The Centurion RT features true online double conversion. As our highest single phase power density UPS, this sophisticated range will provide the most comprehensive protection for mission critical devices such as sensitive networks, computers, servers, telecom applications, as well as industrial applications.
Meticulously developed by PowerShield engineers to be a world leading technology UPS, the Centurion RT addresses absolutely all requirements and features as has been demanded by the sophisticated Australian power consumer and hence stands in a class of its own, as a world leading UPS technology.

- Exceptional surge protection
- Unity Output power factor (PF=1)
- Informative & easy-shift LCD display
- Rack/Tower design
- Emergency Power Off Function (EPO)
- ECO & advanced ECO mode
- Standard extra large charger
- Hot swappable batteries

Specifications

Technical Specifications

Voltage Range Line Loss 110~300Vac @ (0~60%) Load; 140~300V @ (60~80%) Load; 176~300Vac @ (80~100%) LoadLow Line Comeback Low Line Loss Voltage + 10VHigh Line Comeback High Line Loss Voltage - 10V
Frequency Range 46Hz ~ 54 Hz @ 50Hz system; 56Hz ~ 64 Hz @ 60Hz system
Phase Single phase with ground
Input Power Factor Correction Less than or Equal to 0.99 @ nominal voltage (100% load)
Output Voltage 208 / 220 / 230 / 240VAC AC Selectable
AC Voltage Regulation ± 1%
Frequency Range (Synchronized Range) 46Hz ~ 54 Hz @ 50Hz system56Hz ~ 64 Hz @ 60Hz system
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Overload AC Mode 100%~110%: 10min ; 110%~130%: 1min ; >130% : 1secBattery Mode 100%~110%: 30sec ; 110%~130%: 10sec ; >130% : 1sec
Current Crest Ration 3:1 Max
Harmonic Distortion Less than or Equal to 1 % @ 100% Linear Load; 4% @ 100% Non-linear Load
Transfer Time Line to Battery 0 msInverter to Bypass 0 msInverter to Eco < 10 ms
AC Mode > 94%
Battery Mode > 93%
Battery Type Depending on applications
Battery Number Optional strings of 16 or 20 batteries
Typical Recharge Time According to external battery pack
Charging Current (max.) 4 A ± 10%
Interface USB and RS232 as standard
Software PowerShield® NetGuard® software - supports Windows, Linux, Unix and Mac based operating systems
Optional Intelligent slot for PSSNMPV4, PSModbus or PSAS400 dry contact
Temperature 0 ~ 40°C
Humidity 95% (RH Non-condensing)
Altitude <1000m